|
Water Treatment Non-chemical Device "The Dolphin HYTRONIC Series 1000" pulsed power water treatment device (Dolphin) Manufactured by Clearwater Systems LLC 145 Dennison Rd. P.O. Box 463 Essex, CT 06426 phone: 860-767-0850 FAX 860-767-8972 http://www.clearwater-dolphin.com/
System Data
Boilers
Cooling Towers
Claims Made
History PCT personnel visited the site twice in January 2003 to examine an opened boiler, check the cooling towers, and obtain water samples. The site visits were at the request of hospital operating personnel as they had determined, based on their experience with the NCD units, to return to chemical treatment in the near future. During the visits, plant personnel reported that, at threaded joints, boiler piping leaks started within three months of start-up, with many parts of both the feedwater and blowdown piping being repaired as many as three times prior to the PCT visit. Problems reported with the cooling towers included chunks of rust scale blocking distributor nozzles, "rusty" appearance of the cooling water at times, biological buildup in condenser heads, and excessive brushing of tubes to maintain chiller operation. A corrosion coupon rack was installed, but hospital personnel had received no results to date from Clearwater. Target conductivity, controlled by a conductivity base blowdown controller, was 1000 mmhos, giving about 4.5 cycles.
Review Our examination showed what appeared to be severe oxygen pitting corrosion at the fire side tube/tube sheet junction. Examination of the boiler water side internals showed definite oxygen pitting corrosion with a substantial coating of fine red/black powder on all surfaces. Several leaking pipe joints, corrosion evident, on the condensate, feedwater, and blowdown piping were also observed. Plant operators noted that boiler #2 had logged just 1300 hours of operation. The cooling tower system came on-line during the first visit with the cooling water observed to be very rusty, looking like tomato juice. Almost immediately, the cooling tower was seen to overflow from the distribution deck. Inspection of the deck showed that the overflow was the result of large pieces of rust scale blocking the distributor nozzles. Samples were obtained only from the boiler system (boiler #1 on-line) as the cooling system was operating under upset conditions. Analytical results from Analytical Services, Inc., Brockway, PA, a state certified laboratory, are attached. A Dolphin unit control box was opened and found to contain a small transformer. The transformer output, passing through an inductor coil, fed into the actual Dolphin unit. The Dolphin unit was also inspected and appeared to be nothing more than an insulated wire coil wound around a pipe spool. Typical power input was listed on the literature as 110 to 390 va. Draining of Y screen traps prior to the condensate pumps, and the condensate and feedwater sample ports, resulted in a substantial amount of black and yellow red solids discharge.
Discussion While not of the same magnitude as iron, the high level of copper, 2.9 mg/l, in the boiler water is also of concern as it indicates corrosion of yellow metals somewhere within the boiler system. While the calcium level in the boiler water was somewhat lower than expected, no calcium scale was seen in the water side inspection of boiler #2. It appears that the calcium is bulk precipitating in the boiler water due to the substantial loss of alkalinity and the presence of some phosphate in the city makeup water. In essence, the boiler is actually operating on a combined carbonate/phosphate cycle bulk precipitation program, which explains the lack of any substantial scale deposits. Levels of both magnesium and silicon in the boiler water are substantially lower than would be expected based on the ten (10) chloride cycles that the boiler was operating at when sampled. This indicates that magnesium silicate is also precipitating within the boiler. While the condensate pH was lower than the desired 8.0 to 8.5 su range, it was not strongly acidic and did not contain a substantial amount of iron. This can be explained given the low alkalinity of the makeup water, 15 mg/l, and the loss of alkalinity within the boiler due to calcium precipitation, which ties up carbonate preventing evolution of carbon dioxide into the steam with subsequent condensation as carbonic acid.
Conclusions While no calcium scale is evident in the boiler, the analytical data shows that the actual mechanism preventing scale formation is classic carbonate cycle boiler chemistry aided by phosphate present in the city water. We would thus conclude that the Dolphin NCD has no evident effect on scale.
Cooling Tower Looking at control of scale, operating with city water at 1000 mmhos, about 4.5 cycles of concentration, results in a saturation index of -0.35 at 95 F. Basically, under these non-scaling conditions, no scale could form, thus we cannot comment on the ability of the Dolphin unit to control scale in a cooling water application.
Literature For instance, reference is made to Faraday's Law of Magnetic Induction1 to "explain" how the Dolphin unit "affects surface charge and precipitation." This law concerns induction of an electrical voltage via movement of a magnetic field relative to a conductor. At no place in the equation for this law, εmf= -λ ( δφB /δt)  can one find an addition, or removal, of an electron to a particle, which would be required to affect the surface charge of a particle. Dolphin literature further states operation is via “The electric field affects the surface charge and precipitation behavior of charged particles--”. It is a commonly accepted chemical principal that the constituents responsible for scale formation exist in water as separate, hydrated ions, not as “charged particles”. Since there are no particles in the water to be “affected” by an electric field, there will be no action by the NCD. The claimed "activation of colloidal nucleation sites" resulting in bulk water precipitation of calcium carbonate is easily explained by well known chemical processes, operating with, or without, the presence of the Dolphin NCD.
Economics Reducing the cost of the Dolphin installation by that of the chemical feed and control equipment gives a cost of $72,068, which results in a simple ROI of 11.4 years for replacement of the chemical water management program by the Dolphin NCD. This is an extremely poor ROI and cannot justify installation of such a NCD, even if it did work as claimed. Please note that we did not consider the costs of such items as makeup and blowdown in the above simple ROI review as the chemical water management program would operate, in both the boiler and cooling tower systems, at substantially higher cycles than was specified for the Dolphin installation. This would effectively give a lower operating cost due to reduced makeup and blowdown, further increasing the Dolphin ROI time period. ReporterTimothy Keister, FAIC, CWT Chief Chemist
Specific Faraday law noted in letter dated July 24, 2003, from Robinson & Cole, attorneys for Clearwater Systems, LLC.
Boiler Water Analysis Report
|