An Industrial Case History Report Replacement of Chlorine Dioxide at a Large Sintered Metal Parts Plant
History While the chlorine dioxide was successful in controlling the microbiological problem, it created new problems due to the hazards of safely handling and using chlorite and chlorine dioxide solutions. In one accident, a plant employee was hospitalized for a week due to respiratory problems resulting from inhalation of chlorine dioxide fumes.
Results Biological control, with the EBG-2 replacing the chlorine dioxide, has been judged to be visually the same, or better. This observational data has been verified by routine ATP test data from monthly service calls. A mean ATP of 362 rlu, std. dev. of 238, was obtained when operating with chlorine dioxide. The data when operating with the ElectroBrom unit shows a mean of 298 rlu, std. dev. of 114.
The following corrosion coupon results, mean of 19 sets of coupons, were obtained during operation with chlorine dioxide:
One set of coupons have been analyzed since conversion to the ElectroBrom Biocide System with the following results obtained:
This corrosion coupon data shows that the excellent corrosion control at this plant when operating with chlorine dioxide has been maintained after conversion to the ElectroBrom Biocide System. The plant is very pleased that the ElectroBrom Biocide System has controlled biological growth while eliminating a safety problem. The precursor salt solution used, PCT 3024, is DOT/OSHA non-hazardous, while the produced bromine solution is also OSHA non-hazardous. PCT 3024 is registered with the USEPA as a biocide precursor, registration #58616-1.
|